Publication: Grid-connected induction generator interturn fault analysis using a PCA-ANN-based algorithm
| dc.contributor.author | TERZİ, ÜMİT KEMALETTİN | |
| dc.contributor.authors | Bayar, Haydar; Terzi, Umit Kemalettin | |
| dc.date.accessioned | 2022-04-25T00:10:58Z | |
| dc.date.accessioned | 2026-01-11T18:08:59Z | |
| dc.date.available | 2022-04-25T00:10:58Z | |
| dc.date.issued | 2016 | |
| dc.description.abstract | It is difficult for short circuits among the internal windings of one phase in electrical machines to be determined in a reliable and speedy manner. The failure currents that occur, especially in short circuits with a few windings, are at such low levels that they cannot be determined by relay systems. This results in growing faults and damage. In this study, we designed a model that can define winding failures successfully at very small levels by using the PCA and ANN algorithms. We tested the real-time faults and measured the system performance with the installed test rig. The developed protection model determined fault determination in very small (2.5%) winding failures with acceptable accuracy. The suggested model is a counter-speed, selective, flexible, and economical protection model that may be used for internal failures of electrical machines. It has a structure that may be used in different systems or kinds of failure with data receiving and software changes. | |
| dc.identifier.doi | 10.3906/elk-1312-145 | |
| dc.identifier.eissn | 1303-6203 | |
| dc.identifier.issn | 1300-0632 | |
| dc.identifier.uri | https://hdl.handle.net/11424/263810 | |
| dc.identifier.wos | WOS:000374121500046 | |
| dc.language | eng | |
| dc.publisher | TUBITAK SCIENTIFIC & TECHNICAL RESEARCH COUNCIL TURKEY | |
| dc.relation.ispartof | TURKISH JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTER SCIENCES | |
| dc.rights | info:eu-repo/semantics/openAccess | |
| dc.subject | PCA | |
| dc.subject | induction generator | |
| dc.subject | faults | |
| dc.subject | protection | |
| dc.subject | WIND TURBINE | |
| dc.subject | PROTECTION ALGORITHM | |
| dc.subject | FIXED-SPEED | |
| dc.subject | SYSTEM | |
| dc.subject | PERFORMANCE | |
| dc.subject | DIAGNOSIS | |
| dc.title | Grid-connected induction generator interturn fault analysis using a PCA-ANN-based algorithm | |
| dc.type | article | |
| dspace.entity.type | Publication | |
| oaire.citation.endPage | 1350 | |
| oaire.citation.issue | 3 | |
| oaire.citation.startPage | 1340 | |
| oaire.citation.title | TURKISH JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTER SCIENCES | |
| oaire.citation.volume | 24 |